Reverse Tempering Emergency Equipment Water

Feb. 18, 2004
With advances in emergency shower and eyewash technology, water temperatures are not too hot, not too cold ... just right.

One could make a strong case that the invention of the emergency shower and eyewash were among the greatest advancements in industrial employee safety over the past 50 years. In fact, it's difficult to imagine how we operated prior to their introduction. They certainly revolutionized employee and employer peace-of-mind in hazardous material environments, to say the least.

Those early system designs, however, did not take into account the comfort and, to a point, the safety of the people who used them. Exposure to the significant volumes of water used in this equipment during a full duty cycle can be uncomfortable and even dangerous, if it is outside of a specific temperature range either too cold or too warm.

More recently, the science of emergency equipment design and application has begun to more stringently recognize that temperature range. For the past several years, water temperatures below about 80 degrees Fahrenheit (26 C) have begun being addressed through engineered solutions referred to as "Tempered Water" packages. Using sophisticated, self-contained monitoring capabilities, tempered water systems blend hot and cold input water to maintain a prescribed temperature through a full-duty cycle. The best of these systems also provide a guard-band measure that by-passes the blending configuration in the event of either a cold or hot water input failure. This eliminates the possibility of scalding, while also assuring the availability of some degree of shower use if at all possible.

What should the specific high and low limits of the temperature range be? The guidelines used by the Haws Corp. are 80 degrees Fahrenheit (26 C) on the low end and 95 degrees Fahrenheit (35 C) on the high end. These are not "official" limits, as ANSI does not publish standards for temperature. Safety engineers are encouraged to seek medical counsel for specific range limitations given their individual circumstances. That said, using these range limits, any input water below 80 degrees Fahrenheit (26 C) would require tempering (warming) and any input water exceeding 95 degrees Fahrenheit (35 C) would require reverse tempering (cooling).

While much attention has been paid recently to tempered water, not nearly as much has focused on reverse tempering.

Solutions for Hot Showers in Severe Climates

As mentioned, colder climates with cold input water conditions can have a serious effect on emergency equipment operation and user comfort. Emergency equipment manufacturers have, through the years, designed equipment and option packages that address the lower limits of the operating temperature range. But, as severe as cold climate conditions can be, summer or hot climate conditions can produce excessively high water temperatures in the safety equipment.

In warmer regions of the world, it is common to experience water temperatures in excess of 100 degrees Fahrenheit (38 C). At those temperatures, it is possible for the hot water to amplify the burning pain associated with a chemical exposure, for example. When input water temperatures become a concern, there are several options to cool things down:

Option 1: Hot water at shower piping, but cool water supply from ground.

(Example: Above-ground piping, exposed to direct sunlight in Houston)

In facilities where the safety shower supply piping is exposed to extreme ambient temperatures, but the ground supply temperature is lower, we specify a central chilling package that serves a safety shower loop. This engineered solution provides a package containing the chiller equipment and a recirculation pump to continuously chill the loop water. The recirculation pump moves the water throughout the loop at a low flow rate, which passes it through the central chiller to drop the water down from the ambient temperature to 80 degrees Fahrenheit (26 C). This process continues throughout the day until the ambient temperatures have no effect on the loop, at which time the system stops the chilling process.

Option 2: Hot water at shower, and hot water supply.

(Example: Shower and/or eyewash installation in Saudi Arabia)

This scenario is the same as above, but now when a shower is activated, the incoming water supply is also hot. To combat this problem, a storage tank is included in the package, sized for the number of safety showers operating simultaneously. The storage tank will be in-line with the chiller so that the recirculation pump will push the chilled water through the tank and out to the safety showers. You now have a safety shower loop that is maintained at a comfortable level with a storage capacity large enough to supply your shower or showers. As a shower is activated, the user will be guaranteed a cool and comfortable shower for the required 15-minute drench.

Option 3: Other engineered solutions.

(Examples: A semi-portable, self-contained (closed) system or an air-charged system or an application calling for a climate-controlled booth)

While many requests deal with supply water heated by nearby industrial processes or pipes exposed to the sun (option #1) or simply a hot water supply in a hot climate (option #2), there are other specific needs and one-off applications that can be encountered. For instance, in either of the first two options, the required chiller would most likely be centralized to feed cool water to several showers and/or eyewashes. Alternatively, a semi-portable single shower application might feature a closed loop system, designed with a smaller chiller and re-circulation pump integrated into its design. The same approach might be appropriate for an air-charged, closed-loop system used in a remote location. Under certain circumstances, housing an entire stand-alone shower system in a climate-controlled enclosure might be the best approach. The point is that there are many ways to address reverse tempering challenges. The "best" one is the one that works best for you!

For more information about reverse tempering of emergency equipment, please visit www.hawsco.com/ag.

Randall Hall is a staff engineer at Haws Corp., located in Sparks, Nev. He can be reached at (775) 353-8367 or at [email protected]. Haws Corp. designs, manufactures and distributes drinking fountains and emergency equipment.

Sponsored Recommendations

Unleashing the Power of Stories: Level-up Safety Culture with Three Easy Storytelling Tools

Jan. 3, 2025
Effective storytelling can shape a workplace culture and improve safety, especially in times of change when risk soars, hazards multiply and human factors threaten to derail progress...

4 Resources to Get Better Safety Performances From Supervisors

Jan. 3, 2025
Here is an overview of four of the best safety resources that safety folks can use as they consider how to get better safety performances from supervisors and workplace leaders...

4 Often Overlooked Types of New Workers—and the Different Dangers They Face

Jan. 3, 2025
This blog post is an adapted excerpt from the safety guide Fitting in Fast: Making a Safe Workplace for New Hires, which examines data and best practices regarding the protection...

4 Ways Frontline Supervisors Influence Workplace Safety

Jan. 3, 2025
These four areas determine whether frontline supervisors are having a positive or negative effect on workplace safety.

Voice your opinion!

To join the conversation, and become an exclusive member of EHS Today, create an account today!